Skip to content
Contact us
Literature

Gitié ACAY

Trivalent integrated outdoor package with gas absorption chiller and condensing boiler.

For heating, hot water production up to 80°C and cooling with minimum electric consumption.

Gitié ACAY can provide up to 3 services:

  • heating;
  • hot water production up to 80°C;
  • cooling with minimum electric consumption.
Gitié ACAY

Benefits

  • Gitié, integrated, pre-assembled and custom-made in the manufacturing plant, is a fully plug-‘n-play system. This can facilitate correct installation, avoiding the complexity of the integration on field of solar thermal systems.

Versions

Available in standard and low-noise versions, 2 and 4-pipe, with or without circulators.

Applications

  • Ideal for residential, industrial, commercial and hospitality facilities.
  • Suitable for both new and existing buildings as it’s for fitting in heating systems with low temperature (radiant heating or fan coils) or high temperature (radiators) distribution systems.
  • Outdoor installation.

Technical table

Energy class ErP (55 °C operation): A
Heating capacity – condensing boiler (water 80/60 °C)(1)kW 34.4
Efficiency – condensing boiler (50/30 °C): 104.6%
Maximum outlet water temperature heating/DHW: 80/80°C
Outdoor operating temperature (dry bulb) - max/min: 45/-20°C
Cooling capacity (A35/W7): kW 17.72
G.U.E. gas utilization efficiency (A35/W7): 71%
Minimum outlet water temperature: 3°C
Inlet water temperature max/min: 45/6°C
Nominal electrical consumption (2)(3) - standard version: kW 1
Nominal electrical consumption - low noise version: kW 1.05
Sound power Lw(4) - standard version: dB(A) 82.1
Sound power Lw - low noise version: dB(A) 76.1
Sound pressure Lp at 5 metres(5) - standard version: dB(A) 60.1
Sound pressure Lp at 5 metres - low noise version: dB(A) 54.1

(1) Nominal conditions according to EN 12309-2.
(2) ± 10% tolerance depending on the electric voltage and engine consumption.
(3) Version with circulators: 240 W extra.
(4) Sound power levels measured according to EN ISO 9614.
(5) Free field, front, direction factor 2.

Controllers

DDC

DDC

Robur Box 100

Robur Box 100

Robur Box 200

Robur Box 200

Pannello Comfort Control Interface (CCI)

Pannello Comfort Control Interface (CCI)

Literature