NEXT-G
Heat output Next-G 30: nominal kW 27.4 - minimum kW 9.9
Heat output Next-G 45: nominal kW 41.4 - minimum kW 14.5
Heat output Next-G 60: nominal kW 56.6 - minimum kW 19.5
Heat output Next-G 90: nominal kW 87.3 - minimum kW 28.6
Efficiency Next-G 30: nominal heat input 97.8% - minimal heat input 106.8%
Efficiency Next-G 45: nominal heat input 96.2% - minimal heat input 105.3%
Efficiency Next-G 60: nominal heat input 97.5% - minimal heat input 105.2%
Efficiency Next-G 90: nominal heat input 97.0% - minimal heat input 106.1%
Air flow - nominal (ΔT = 15 °C) Next-G 30: max. 2,450 m3/h
Air flow - nominal (ΔT = 15 °C) Next-G 45: max. 3,450 m3/h
Air flow - nominal (ΔT = 15 °C) Next-G 60: max. 5,660 m3/h
Air flow - nominal (ΔT = 15 °C) Next-G 90: max. 9,100 m3/h
Electrical power absorption Next-G 30: kW 0.21
Electrical power absorption Next-G 45: kW 0.35
Electrical power absorption Next-G 60: kW 0.61
Electrical power absorption Next-G 90: kW 1.00
Ambient air temperature (minimum/maximum): 0/40 °C
Flue gas exhaust - diameter (Ø): mm 80
Combustion air intake connection - diameter (Ø): mm 80
NEXT-G C
Air flow Next-G 30 C: at maximum available head: m3/h 2,500 - free blowing: m3/h 3,500
Air flow Next-G 60 C: at maximum available head: m3/h 5,400 - free blowing: m3/h 6,500
Maximum useful pressure head Next-G 30 C: Pa 140
Maximum useful pressure head Next-G 60 C: Pa 120
Minimum pressure drop on heat flow delivery: Pa 0
NEXT-G EC
Heat output Next-G 20 EC: nominal kW 19.0 - minimum kW 8.5
Heat output Next-G 30 EC: nominal kW 27.4 - minimum kW 9.9
Heat output Next-G 35 EC: nominal kW 33.4 - minimum kW 13.1
Heat output Next-G 45 EC: nominal kW 41.4 - minimum kW 14.5
Heat output Next-G 60 EC: nominal kW 56.6 - minimum kW 19.5
Heat output Next-G 75 EC: nominal kW 72.0 - minimum kW 26.2
Heat output Next-G 90 EC: nominal kW 87.3 - minimum kW 28.6
Efficiency Next-G 20 EC: nominal heat input 97.5% - minimal heat input 105.5%
Efficiency Next-G 30 EC: nominal heat input 97.8% - minimal heat input 106.8%
Efficiency Next-G 35 EC: nominal heat input 96.9% - minimal heat input 106.5%
Efficiency Next-G 45 EC: nominal heat input 96.2% - minimal heat input 105.3%
Efficiency Next-G 60 EC: nominal heat input 97.5% - minimal heat input 105.2%
Efficiency Next-G 75 EC: nominal heat input 96.0% - minimal heat input 105.0%
Efficiency Next-G 90 EC: nominal heat input 97.0% - minimal heat input 106.1%
Air flow - nominal (ΔT = 15 °C) Next-G 20 EC: max. 2,300 m3/h
Air flow - nominal (ΔT = 15 °C) Next-G 30 EC: max. 2,450 m3/h
Air flow - nominal (ΔT = 15 °C) Next-G 35 EC: max. 2,735 m3/h
Air flow - nominal (ΔT = 15 °C) Next-G 45 EC: max. 3,450 m3/h
Air flow - nominal (ΔT = 15 °C) Next-G 60 EC: max. 5,650 m3/h
Air flow - nominal (ΔT = 15 °C) Next-G 75 EC: max. 5,400 m3/h
Air flow - nominal (ΔT = 15 °C) Next-G 90 EC: max. 9,100 m3/h
Electrical power absorption Next-G 20 EC: kW 0.19
Electrical power absorption Next-G 30 EC: kW 0.19
Electrical power absorption Next-G 35 EC: kW 0.18
Electrical power absorption Next-G 45 EC: kW 0.39
Electrical power absorption Next-G 60 EC: kW 0.41
Electrical power absorption Next-G 75 EC: kW 0.39
Electrical power absorption Next-G 90 EC: kW 0.75
Ambient air temperature (minimum/maximum): 0/40 °C
Flue gas exhaust - diameter (Ø): mm 80
Combustion air intake connection - diameter (Ø): mm 80